求翻译:断开变频器和电机的连线,运行变频器在50Hz,用万用表检查三相输出U、V、W之间是否有均衡的交流电压。注意,由于U、V、W之间是高频脉冲,请选用模拟电压表测量(量程为交流500V) 。如果电压不均衡或没有电压,则变频器模块损坏。是什么意思?

待解决 悬赏分:1 - 离问题结束还有
断开变频器和电机的连线,运行变频器在50Hz,用万用表检查三相输出U、V、W之间是否有均衡的交流电压。注意,由于U、V、W之间是高频脉冲,请选用模拟电压表测量(量程为交流500V) 。如果电压不均衡或没有电压,则变频器模块损坏。
问题补充:

  • 匿名
2013-05-23 12:21:38
Disconnect the connection to the inverter and the motor, inverter to run in 50hz, three-phase with a multimeter to check the output u, v, w between a balanced AC voltage. Note that u, v, w is the frequency pulse, please use the analog voltmeter (range AC 500v). If the voltage is not balanced or no v
  • 匿名
2013-05-23 12:23:18
Disconnect the motor drive and run the converter, in 50, with 10,000 Hz check 3 Phase Output, V U W , whether there is balance of the AC voltage. Note that because U , V W , is between high-frequency pulse, please use analog voltage measurements (range 500 V) for the exchange. If the voltage is not
  • 匿名
2013-05-23 12:24:58
Separates the frequency changer and the electrical machinery segment, moves the frequency changer in 50Hz, three-phase outputs U with the avonmeter inspection, V, between W whether has the balanced alternating voltage.Attention, because U, V, between W is the high frequency pulse, please select the
  • 匿名
2013-05-23 12:26:38
Disconnect the inverter and motor connection, run the converter on 50Hz, with a multimeter check for three-phase output u, v, w are balanced between the AC voltage. Note that since u, v, w are high frequency pulses, use the analog voltage meter (quantum AC 500V). If the unbalanced voltage or no volt
  • 匿名
2013-05-23 12:28:18
正在翻译,请等待...
 
 
网站首页

湖北省互联网违法和不良信息举报平台 | 网上有害信息举报专区 | 电信诈骗举报专区 | 涉历史虚无主义有害信息举报专区 | 涉企侵权举报专区

 
关 闭